Abnormal Superheat — Low / High Diagnosis
Likely causes
Superheat too low (<5°C / 9°F) — risk of liquid refrigerant flooding compressor
Check: Attach clamp thermometer to suction line + read low-side pressure on manifold gauge. Convert pressure to saturation temperature via PT chart → measured temp − saturation temp = superheat. Normal range: TXV systems 8–12°C (15–20°F), capillary systems 4–7°C (8–13°F).
What to do: 1) Inspect TXV sensing bulb position — clamp at 4 or 10 o'clock on suction line, wrap with insulation. 2) Adjust TXV superheat screw clockwise (raises superheat) by 1/4 turn only — wait 30 min after each turn to stabilize. 3) If overcharge suspected, recover and recharge by weight. Liquid slugging causes immediate compressor valve failure — stop unit immediately.
Superheat too high (>15°C / 27°F) — undercharge or TXV restriction
Check: Calculate superheat using same method above. Simultaneously check liquid line sight glass — bubbles/flash gas indicate undercharge. Discharge pressure also runs low (mimics low-load operation).
What to do: 1) Leak check first — use electronic detector or soap solution on all flares, brazed joints, service valves. 2) After repair, evacuate 30 min + recharge by weight. 3) If TXV restriction suspected, disassemble/clean or replace — always replace filter-drier together. 4) Never just top off refrigerant — adding charge without leak repair violates regulations and guarantees recurrence.
Superheat measurement requires simultaneous temperature + pressure reading at the same suction line point. Don't measure right after shutdown — wait at least 15 min of stable operation.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Superheat Hunting — TXV Oscillation
- Superheat Cannot Be Measured — Gauge or Thermometer Reliability Failure
- Abnormal Subcooling — Low / High Diagnosis
- Zero Subcooling — Continuous Bubbles in Liquid Sight Glass
- PT Chart Usage — Pressure↔Temperature Conversion Diagnosis
- Refrigerant Type Cannot Be Identified — Missing Nameplate or Painted Over