R-Pro › Field cases › Air conditioning
Foul Odor When Unit Operates
Likely causes
Mold and bacteria growth — moisture on evaporator coil and drain pan
Check: Remove indoor unit front panel, visually inspect coil and drain pan — black or green discoloration indicates mold. Use flashlight to check for slime deposits between coil fins.
What to do: 1) Apply antibacterial coil cleaner → let stand 30 min → rinse with water. 2) Remove drain pan, clean with 50°C water + neutral detergent. 3) Install antimicrobial pad (silver-ion or photocatalyst type) to prevent recurrence. Annual professional AC cleaning recommended.
Burning smell — overheating electrical components (coil, wiring)
Check: Stop unit immediately. After power off, visually inspect electrical components — burn marks (brown/black), melted insulation. Measure motor winding resistance (imbalance >10% = faulty).
What to do: Never restart with burning smell — electrical fire risk. Identify burned components (motor, PCB, wiring) and replace. Measure insulation resistance between winding and case with 500V megger (≥1MΩ is acceptable). After replacement, re-verify running current is normal.
Refrigerant leak odor — sweet chemical smell
Check: Immediately open windows and ventilate. Locate leak source with electronic refrigerant leak detector. Check refrigerant pressure with low-side gauge — lower than normal confirms leak.
What to do: Repair leak (re-flare, re-braze) → nitrogen pressure test (1.5 MPa, 24h) → vacuum (below 500μmHg, 30 min) → recharge to specified amount. HFC refrigerants (R-410A, R-32, etc.) must be handled only by licensed technicians.
Mold odor is especially strong on first cooling operation. One coil cleaning before summer season can prevent it throughout. Burning smell is a fire precursor — never ignore it.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Unit Completely Inoperative
- Various Abnormal Noises During Operation
- Water Dripping from Indoor Unit / Poor Drainage
- Inverter PCB IGBT Module Burnout (E6/H6 Error)
- BLDC Outdoor Fan Motor Burnout (Bearing Wear → Overcurrent Trip)
- PFC Circuit Electrolytic Capacitor Swelling (Increased Ripple Current → Capacitance Drop)