Unit Completely Inoperative
Likely causes
Circuit breaker (NFB) tripped — overload or electrical surge
Check: Check dedicated AC breaker at distribution panel — verify if it is in trip position (middle). Measure primary voltage with multimeter (within ±10% of rated).
What to do: 1) Identify trip cause (megger test compressor insulation, inspect wiring for shorts). 2) Resolve cause, then reset breaker OFF→ON. Never reset immediately — fire hazard if root cause unresolved.
Faulty start capacitor
Check: Measure capacitance (μF) with LCR meter or multimeter in capacitor mode. Faulty if deviation exceeds ±6%. Visually check for swelling or electrolyte leakage.
What to do: Replace with same rating (μF, voltage). Discharge residual voltage across terminals before replacement (short with insulated screwdriver). Classic symptom: humming sound with fan/compressor not spinning.
Unstable power supply — low voltage or single phasing
Check: Measure each phase-to-phase voltage with multimeter. Faulty if deviation exceeds ±10% of rated or phase imbalance >3%. For single-phase units, check L-N voltage.
What to do: Request electrical contractor to resolve supply voltage issue. Automatic voltage regulator (AVR) can be installed as temporary measure. Single phase detected: stop unit immediately — compressor winding burnout risk.
Thermostat power failure or dead batteries
Check: Check if thermostat display is lit. For battery-powered units, measure battery voltage (AA ≥1.5V). For wired units, verify terminal supply voltage (typically 24VAC or 12VDC).
What to do: Replace batteries (new AA ×2). For wired: inspect control circuit fuse and wiring. If display is normal but command not transmitted, re-tighten wiring terminals or replace thermostat.
Safety interlock activated — low/high pressure cutout or overload trip
Check: Check controller error code. Verify low pressure switch terminal continuity with multimeter. Measure low-side pressure with gauge (R-410A cooling minimum 0.3 MPa required).
What to do: 1) Low pressure cutout: refrigerant shortage → detect leak and recharge. 2) High pressure cutout: check outdoor unit heat rejection (clean coil) or refrigerant overcharge. 3) Overload trip: resolve cause, then manually reset. Never repeatedly reset without resolving root cause.
Faulty capacitor classically causes humming sound with fan/compressor not spinning. If no LCR meter, multimeter capacitor mode gives a quick reading.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Various Abnormal Noises During Operation
- Water Dripping from Indoor Unit / Poor Drainage
- Foul Odor When Unit Operates
- Inverter PCB IGBT Module Burnout (E6/H6 Error)
- BLDC Outdoor Fan Motor Burnout (Bearing Wear → Overcurrent Trip)
- PFC Circuit Electrolytic Capacitor Swelling (Increased Ripple Current → Capacitance Drop)