AC Indoor Coil Frost — Insufficient Airflow / Undercharge

Likely causes

Identify frost cause (filter, blower, coil fouling, refrigerant)

Check: Coil surface = white frost or ice thickness. Power OFF 1 hour natural defrost → restore flow. Airflow <50% of normal = filter/blower fault. Normal airflow but frost = undercharge (suction below normal) or EEV stuck closed. Ambient >35°C with indoor setpoint <26°C = operating limit exceeded, frost possible.

What to do: Action per cause: filter/blower = clean/replace. Coil fouling = professional coil cleaner. Undercharge = trace leak then recharge by weight. EEV = diagnose/replace coil. Operating limits = educate user (≥26°C setpoint). Never use dryer/heat gun for defrost = damages aluminum fins.

Field tip

Recurring frost = accumulating damage (liquid slug, coil corrosion). One occurrence = resolve cause immediately + monitor. ≥2 events per season = full system diagnostic. Educate user: turn OFF immediately when frost seen and call service.