R-Pro › Field cases › Air conditioning

AC Pressure Sensor (High/Low) Fault

Likely causes

Identify sensor type (switch / analog transducer)

Check: Switch type = on/off at threshold (resistance 0 Ω ↔ ∞). Transducer = with 5VDC supply, outputs 0.5–4.5V proportional. Refer to manual for pressure → voltage table. Compare actual pressure (manifold) vs PCB reading — deviation >±10% = sensor bad.

What to do: Measure actual manifold pressure and PCB reading simultaneously. Deviation >±10% = sensor bad. Replace with same spec and pinout. Transducer = verify DC 5V supply, measure output. After replacement, run learning or self-diagnostic mode to confirm recognition.

Field tip

Faulty high-pressure sensor = false high-pressure cutouts. Faulty low-pressure = false undercharge diagnosis. Replace with same spec/pinout. Some models legally require these protections — never bypass.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases