R-Pro › Field cases › Air conditioning
AC Temperature Sensor (Thermistor) Failure
Likely causes
Identify fault by sensor location (indoor, evap, outdoor, condenser, discharge)
Check: Thermistor = NTC type, typically 5 kΩ or 10 kΩ at 25°C. Measure resistance → compare with B-constant table (B25/85, typically 3950 or 3435). Open = ∞, short = 0 Ω, drift = ±20% off table. Cable = check open/contact.
What to do: Replace with same spec (resistance + B-constant must match). Mount per location (heat exchanger coil clip or discharge pipe contact). Apply thermal grease for pipe contact. Cable open = new cable or extension. Activate learning mode after replacement (inverter type).
Thermistor fault = most common cause behind PCB-error codes (sensor is the culprit more often than the PCB). Before replacing = check cable open/connector loose. R-32/R-410A compatible = use high-temp grade on discharge (>120°C).
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →