R-ProField casesAir conditioning

AC Weak Cooling — Outdoor Fan Stopped / Slow Speed

Likely causes

Step 1 — Check fan motor, capacitor, blade

Check: Fan stopped = discharge pressure spikes → high-pressure cutout within 5 min. Measure motor winding resistance (single-phase 0.5–5 Ω per manual) — ∞ = open. Run capacitor capacitance (within ±6%). Blade = check for insects/bird nest/bent/cracks. Inverter fan = verify PCB DC signal.

What to do: Power OFF + breaker OFF first. Measure motor winding resistance with multimeter (single-phase 0.5–5 Ω, open = ∞). Run capacitor capacitance (within ±6%). Blade = check insect/bird nest/bend/crack. Inverter fan = measure PCB DC output. Identify faulty part, then proceed to replacement step.

Field tip

Summer = bird nests common (dark interior). Pre-season inspection mandatory. Bent/cracked blade = crack expands during rotation, risk of housing damage. Replace immediately. Motor open/cap fault = often replaced as a unit (parts hard to separate).

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases