Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
Likely causes
Refrigerant leak — shaft seal, flange, valve gasket
Check: Connect gauge manifold and check low-side pressure (R-134a normal: 3.5–4 bar; below spec suspects leak). Scan shaft seal, flanges, and service valves in order with electronic leak detector
What to do: Repair leak → evacuate to ≤500 microns for 30+ min → recharge to spec using electronic scale
Expansion valve (TXV/EEV) clogged or faulty
Check: Measure superheat with gauge — TXV clog suspected if >15°C vs normal 5–8°C. Check temperature differential across valve inlet/outlet
What to do: Clean or replace TXV strainer → re-adjust superheat to 5–8°C. For EEV, check controller output signal (0–10V) and step count, then replace if faulty
Filter drier clogged
Check: Measure temperature before and after filter drier — if outlet is 2°C+ colder than inlet, clogged. Check sight glass moisture indicator (yellow = wet, green = dry)
What to do: Replace filter drier (after 1–2 years service or when moisture indicator saturates). Evacuate 30+ min after replacement → recharge
Low pressure switch faulty
Check: Confirm actual low-side pressure with gauge and compare to trip setpoint — if actual pressure is normal but trip occurs, switch is faulty. Confirm with terminal short-circuit test
What to do: Replace LP switch. Temporary operation after short-circuit test is possible but always investigate root cause simultaneously
Persistent sight glass bubbles = low refrigerant. No bubbles but repeated LP trips = likely expansion valve or switch fault.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)
- Screw Compressor Slide Valve Stuck (Partial Load Control Failure)