R-ProField casesAir conditioning

Heat Pump Heating Season Check — Defrost, Outdoor Condensate, Heat Trace

Likely causes

Heating-mode specific items

Check: ① 4-way valve solenoid/pressure balance (separate case) ② Defrost cycle test (run 1 hr, verify auto cycle activates) ③ Outdoor condensate hose = check heat trace function ④ Indoor auxiliary heater (some inverter mini-splits) ⑤ Verify capacity reduction below -10°C ambient (manufacturer table).

What to do: Force 4-way valve mode swap (cool↔heat) test. Verify defrost cycle occurs naturally within 30–90 min. Verify outdoor condensate hose heat trace + freeze protection. For -15°C cold snaps, confirm aux heater operation if applicable. Priority dispatch to elderly/patient households.

Field tip

Korea = mid-Nov to early Dec optimal. Severe cold preparedness (<-15°C) = check heat trace + aux heater. Defrost cycle every 30–90 min normally (model variant). No cycling = diagnose immediately. Elderly/patient households = priority dispatch.