R-Pro › Field cases › Air conditioning

Inverter Overheating from Overload Operation

Likely causes

Compressor overloaded from refrigerant overcharge

Check: Measure ambient temperature (confirm below 43°C)

What to do: Measure ambient temperature (confirm below 43°C) → Measure high/low side pressures → Check for refrigerant overcharge (measure subcooling) → Clean condenser and check fan → Improve machine room ventilation

High compression ratio from elevated head pressure

Check: Measure high/low side pressures

What to do: Measure high/low side pressures → Check for refrigerant overcharge (measure subcooling) → Clean condenser and check fan → Improve machine room ventilation

Ambient temperature too high (above 43°C)

Check: Check for refrigerant overcharge (measure subcooling)

What to do: Check for refrigerant overcharge (measure subcooling) → Clean condenser and check fan → Improve machine room ventilation

Field tip

Heat sink is clean but inverter is overheating. Eliminate the compressor overload cause.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases