R-Pro › Field cases › Air conditioning

Multi-Split Distributor Pipe Sizing Imbalance → Capacity Deviation in Some Indoor Units

Likely causes

Branch pipe diameter mismatch — same-size branch connected to indoor units with different capacities

Check: Check manufacturer piping manual branch diameter table by capacity — e.g. 4.0 kW → Ø9.5 mm, 7.1 kW → Ø12.7 mm. Measure installed branch pipes and compare

What to do: Replace branch pipes in imbalanced sections — upsize piping by one size toward under-supplied indoor units → evacuate ≥30 min → recharge → during commissioning confirm discharge temperature deviation ±2°C

Equivalent length imbalance — certain indoor unit piping equivalent length exceeds 30 m causing excessive pressure drop

Check: Draw full piping diagram and calculate equivalent length for each indoor unit — convert elbows and valves to equivalent lengths. Check if difference between longest and shortest circuit exceeds 15 m

What to do: Measure liquid line pressure at each indoor unit outlet — if deviation ≥0.05 MPa, replace branch pipes or redesign routing. Add U-shaped oil traps in vertical drop sections >15 m (one per 10 m interval)

Field tip

After multi-split installation, commissioning must confirm discharge temperature deviation ±2°C per indoor unit — a larger deviation signals piping imbalance.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases