Air Curtain Insufficient Airflow → 30%+ Cold Air Loss on Door Opening
Likely causes
Partial fan motor failure — one open phase drops RPM, cutting airflow 30–50% from design (1,500–3,000 m³/h)
Check: Measure discharge velocity with anemometer — below 50% of design (4–6 m/s) requires investigation. 3-phase current imbalance >±10% indicates motor replacement
What to do: Replace fan motor. After replacement, verify 3-phase current balance and airflow restored to 4–6 m/s
Air filter blockage — no cleaning for 6+ months reduces airflow 20–40%
Check: Visually inspect filter for dust and fouling. If airflow recovers after cleaning filter, filter was the cause
What to do: Remove and wash filter (aluminum mesh is water-washable) or replace. Set cleaning interval to every 3 months
Belt-drive slip or slack — effective air velocity drops from 4–6 m/s to below 2 m/s
Check: Belt tension check: press center of belt with finger — 10–15 mm deflection is normal; adjust if exceeded
What to do: Readjust belt tension or replace belt. Readjust discharge louver angle to point directly at center of door opening
Air curtain velocity below 4 m/s is almost the same as having none. Below 3 m/s — diagnose and repair immediately. Verify effectiveness: measure temperature change at door bottom 30 s after opening — rise >2°C means insufficient barrier.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Cold Storage / Freezer Temperature Rising
- Walk-in Evaporator Frost Buildup / Defrost Failure
- Cold Storage Compressor Failure to Start / Overload
- Moisture Contamination in Cold Storage System
- Freezer Floor Heating Cable Break → Floor Frost Heave
- Door Gasket Hardening & Shrinkage → Cold Air Leakage (External Condensation Worsening)