R-ProField casesComponents

Ball Valve Internal PTFE Seat Wear — Partial Leakage

Likely causes

PTFE seat wear from repeated open/close cycles

Check: Check for bubbles at valve body and stem with soapy water; isolate circuit and do pressure wedge test across valve (inability to hold differential confirms internal leakage)

What to do: Disassemble ball valve → check PTFE seat ring wear depth (>0.3mm replace) → if ball surface has no mirror finish or visible scratches, replace ball+seat together → use refrigeration-rated valve (no plumbing valves) → stem nut torque 20~25 N·m after assembly

Erosion accelerated by mid-position operation

Check: Check valve handle position — prolonged mid-position use causes concentrated PTFE erosion; ball surface wear shows semicircular (one-side only) damage pattern

What to do: Ball valves must be fully open or fully closed only; replace with globe valve if flow control is needed; improve insulation in systems prone to winter freezing

Field tip

Never leave a ball valve in mid-position. Field cases of seat erosion from throttling are common. Use a globe valve for flow control.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases