Compressor Motor Burnout / Ground Fault
Likely causes
Ground short — winding in contact with compressor shell
Check: Megohm test: measure each winding-to-ground insulation resistance (normal: >1MΩ at 500V DC)
What to do: Replace compressor if insulation fails. Before replacement, analyze root cause — measure system TAN, perform power quality analysis
Open winding / winding-to-winding short — breaker does not trip but motor will not rotate
Check: Measure 3-phase winding resistance with ohmmeter — confirm deviation ≤ ±2%. Open = infinite; short = near 0
What to do: Replace compressor. If acid-contaminated oil: flush system + replace drier + change oil. Before reinstall: pull vacuum to ≤500μm and verify oil charge
Voltage imbalance >2% / liquid refrigerant ingestion — accelerated insulation degradation
Check: Measure all 3 phase voltages → imbalance = (max deviation/average voltage) × 100%. >2% = investigate power supply side
What to do: Resolve voltage imbalance (report to utility). Prevent liquid ingestion: reset TXV superheat to 5~8°C, keep crankcase heater ON at all times
Replacing a burned compressor without fixing root cause leads to repeated failures. Before replacement: power quality analysis + TAN acid measurement. Black carbonized oil = mandatory full system flush.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Liquid Refrigerant Entering Compressor (Flooded Start / Liquid Slugging)
- High Compressor Discharge Temperature (>107°C scroll, >120°C recip)
- Scroll Compressor Reverse Rotation — 3-Phase Miswiring
- Scroll Tip Seal Wear — Volumetric Efficiency Loss and Reduced Cooling Capacity
- Scroll Poppet Valve Fails to Close — Reverse Rotation Noise After Shutdown
- Digital Scroll Solenoid Failure — Loss of 15% Capacity Modulation