R-Pro › Field cases › Components
High Compressor Discharge Temperature (>107°C scroll, >120°C recip)
Likely causes
Low refrigerant — suction gas can't cool the motor windings
Check: Low-side gauge below normal (R-22 normal 4.5–5 bar, below 3 bar = low), bubbles in liquid sight glass, superheat >15°C. Point IR thermometer at discharge line directly — scroll near 100°C = caution, >110°C = stop now
What to do: Leak check first (electronic + spray) → repair leak → full recovery → evacuate 500 micron, 30 min → weigh-in charge. No top-offs. After charging, verify discharge temp below 100°C and superheat 5–10°C
Excessive superheat — TXV/EEV starving or sensing bulb issue
Check: SH = suction line surface temp − low-side saturation temp. >15°C = excessive. Check sensing bulb location (12 o'clock, fully insulated), capillary for oil traces (leak), and TXV adjustment screw position
What to do: Adjust TXV superheat: turn adjustment screw 1/4 turn counterclockwise to lower SH, wait 15 min to stabilize, remeasure. Target: 5–10°C for scroll, 8–15°C for reciprocating. If capillary damaged or bulb leaks, replace TXV assembly. For EEV, verify controller SH setpoint
Poor suction line insulation — heated by hot surroundings
Check: Visually inspect entire suction line — missing, torn, or UV-degraded insulation. Focus on sections passing near boiler/machine rooms. Temp rise >3°C along the line indicates severely insufficient insulation
What to do: Reinstall closed-cell elastomeric insulation (e.g., ArmaFlex) 13–19mm thick over the full length. Glue/tape all seams tightly; add UV jacket where exposed outdoors
Excessive compression ratio — elevated condensing pressure
Check: Calculate absolute high/low pressure ratio — scroll normal 3–5, recip 3–8. Ratio >10 is dangerous. Check simultaneously for condenser fouling, fan failure, rising cooling water temp
What to do: Fix the condensing side — clean condenser, restore fan/cooling water flow, check tower water temp. Consider condenser upsize if undersized. Discharge temp drops automatically once condensing pressure is back to normal
Oil degradation/carbonization — lubrication failure
Check: Inspect oil via sight glass — clear amber = normal; black or cloudy = degraded. Test acidity with test kit — normal green; acidic = yellow. If system ran hot for a long time, oil change mandatory
What to do: Change oil — use manufacturer-specified type and viscosity (never mix POE/PAG/mineral). Drain old oil via drain plug, replace filter drier at same time, run 30 min and recheck. If oil degrades repeatedly, find the root cause (overheating, leak, oil cooler failure)
Measure discharge temp on the pipe surface within 15 cm of the discharge service port using an IR thermometer — the port body itself reads inaccurately. Scroll max 127°C, reciprocating 135°C — always check manufacturer spec, and chase the cause even if it's below max but consistently hot.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Liquid Refrigerant Entering Compressor (Flooded Start / Liquid Slugging)
- Compressor Motor Burnout / Ground Fault
- Scroll Compressor Reverse Rotation — 3-Phase Miswiring
- Scroll Tip Seal Wear — Volumetric Efficiency Loss and Reduced Cooling Capacity
- Scroll Poppet Valve Fails to Close — Reverse Rotation Noise After Shutdown
- Digital Scroll Solenoid Failure — Loss of 15% Capacity Modulation