R-Pro › Field cases › Cooling towers

Blade Pitch Misalignment / Damage

Likely causes

Pitch locking bolts loosened — repeated vibration and thermal cycling

Check: Stop and measure each blade pitch angle with protractor — compare to design (typically 10–12°); also check for overcurrent (pitch imbalance raises current 5–10A)

What to do: Re-torque pitch bolts (M10: 35–40 N·m) → set all blade pitch angles equal → test run and verify current and vibration

Debris impact (leaves/plastic) or FRP blade UV-induced delamination

Check: Visually check FRP blades for cracks, delamination, or deformation — immediately replace if cracks found (no temporary adhesive repairs)

What to do: Replace cracked/delaminated blades immediately → install and inspect debris screens at air inlet → annual inspection of FRP blade UV coating

Field tip

Even one blade with different pitch can raise current draw by 5–10A. Always check blade pitch imbalance when diagnosing overcurrent trips.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases