R-ProField casesCooling towers

Blade Pitch Misalignment / Damage

Likely causes

Pitch locking bolts loosened — repeated vibration and thermal cycling

Check: Stop and measure each blade pitch angle with protractor — compare to design (typically 10–12°); also check for overcurrent (pitch imbalance raises current 5–10A)

What to do: Re-torque pitch bolts (M10: 35–40 N·m) → set all blade pitch angles equal → test run and verify current and vibration

Debris impact (leaves/plastic) or FRP blade UV-induced delamination

Check: Visually check FRP blades for cracks, delamination, or deformation — immediately replace if cracks found (no temporary adhesive repairs)

What to do: Replace cracked/delaminated blades immediately → install and inspect debris screens at air inlet → annual inspection of FRP blade UV coating

Field tip

Even one blade with different pitch can raise current draw by 5–10A. Always check blade pitch imbalance when diagnosing overcurrent trips.