R-Pro › Field cases › Cooling towers

Spray Nozzle Blockage/Misalignment — Uneven Water Distribution

Likely causes

Scale/debris partially blocking nozzle orifice — spray pattern distortion

Check: Visually check each nozzle spray pattern from top basin; start from nozzle above any dry fill zone

What to do: Remove all nozzles → soak 5% citric acid 30 min → clear with pin → replace identical Cv nozzles

Uneven pressure in distribution header — insufficient flow at far-end nozzles

Check: Measure header inlet and far-end pressure — differential >0.05 bar confirms imbalance

What to do: Add equalizing orifice or resize header → high-pressure flush interior (20 bar) → re-measure

Nozzle direction misaligned — water spraying outside fill, uneven fill wetting

Check: Check each nozzle spray direction after stopping — verify aimed at fill center

What to do: Readjust nozzles toward fill center → ensure 10–15% spray pattern overlap when replacing

Field tip

Quickest drift diagnosis: visually check water flow in each zone from top basin. Dry fill zone — inspect nozzle directly above.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases