Blowdown Malfunction — TDS Concentration Buildup
Likely causes
Blowdown motorized valve failure — faulty electrical signal or seized actuator
Check: Measure on-site TDS (conductivity) — above 1500 μS/cm confirms blowdown malfunction; force-open test on blowdown motorized valve
What to do: Immediately perform manual blowdown → if force-open fails, replace valve/actuator → reset TDS setpoint to 1000–1500 μS/cm
TDS controller (conductivity sensor) malfunction or sensor fouled with scale
Check: Remove conductivity sensor → visually check for surface scale; calibration test with 1413 μS/cm standard solution
What to do: Remove sensor scale then calibrate with 1413 μS/cm standard solution → replace sensor if error >±5% → perform manual blowdown at least 3 times per week
TDS 1500 μS/cm equals ~4× concentration ratio — above this level, scale, corrosion, and Legionella risks all rise simultaneously.