R-Pro › Field cases › Chillers

Brazed Plate Heat Exchanger Freeze Fracture

Likely causes

Insufficient water flow (below 30% of rated, < 5 L/min)

Check: stagnant water freezes

What to do: Check water flow: measure inlet/outlet differential pressure (normal 20~40 kPa), confirm flow ≥ 5 L/min with flowmeter

Refrigerant evaporating temperature too low (setpoint error below -10°C, EEV over-open)

Check: Inspect with instruments or visually

What to do: Adjust EEV superheat setpoint: target SH 5~8 K, reduce opening to maintain evap temp ≥ -5°C

Water pump stops under low load while refrigerant continues circulating

Check: residual water freezes

What to do: Verify interlock logic: water pump off → refrigerant pump/compressor off simultaneously

Inadequate pipe insulation in winter

Check: water freezes at plate inlet

What to do: Replace damaged BPHE and reinstall insulation (≥ 25 mm thickness) on inlet/outlet pipes

Poor water quality (scale > 0.5 mm)

Check: flow channel blockage → localized freezing

What to do: Scale inspection: clean annually with 10% citric acid solution circulating for 30 minutes

Field tip

Water-side ΔP > 40 kPa suggests scaling; > 60 kPa requires immediate chemical cleaning.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases