Capillary Tube Blockage — Small Hermetic Refrigerators

Likely causes

Moisture freeze-up — complete blockage at midpoint of capillary

Check: Check for rising high pressure and suction approaching vacuum; if warming capillary with heat gun causes temporary recovery, moisture freeze confirmed

What to do: Recover all refrigerant → nitrogen reverse pressure (5–7 bar) + forward blow to clear blockage → if not cleared, replace capillary with identical spec (same length and ID) + replace drier + vacuum below 1,000 microns

Oil sludge buildup — carbonized oil residue after long operation

Check: Run hand along entire capillary to locate sudden temperature change point — identifies blockage location

What to do: Attempt sludge removal with nitrogen reverse pressure → if ineffective, replace capillary with new identical spec

External crush or kink — pipe damage during service

Check: Visually inspect entire capillary for crush, kink, or flattened section

What to do: Kinked section cannot be repaired → replace entire capillary with identical spec; measure original length with tape before ordering

Field tip

Even 1 cm difference in capillary length affects cooling capacity — always measure original length and replace with identical spec