Centrifugal Chiller Surging — Repeated Impact Noise and Vibration
Likely causes
Refrigerant flow drops below impeller minimum flow (surge line) during low-load operation
Check: Surging is identified by repeated 'bang-bang' impact sounds. Check compressor suction/discharge pressure ratio — below 2.0 indicates surge boundary. Check IGV (inlet guide vane) opening — surging is common when IGV is below 15~20% at loads under 20~30%
What to do: When surging occurs: manually open hot gas bypass valve immediately → increased flow escapes surge line. Set IGV minimum opening to 25~35% — prevent closing below this at low load. After load recovers, gradually close hot gas bypass
Cooling water temperature too low (<25°C) — condensing pressure drops sharply forming surge conditions
Check: Measure cooling water inlet temperature — below 25°C may cause condensing pressure to fall below spec (400~600 kPa depending on model). Check for cooling tower over-cooling in winter or night
What to do: Adjust cooling water temperature control valve — maintain minimum condensing pressure spec. Reduce cooling tower fan speed or stop some cells in winter to maintain cooling water 25~32°C. Check evaporator/condenser tube fouling factor — clean tubes if ≥0.0002
For surging, open hot gas bypass before vibration spikes, then gradually close as load recovers. Ignoring it leads to impeller failure and bearing damage.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)