Chilled Water Glycol Concentration Fault (Freeze Risk)
Likely causes
Insufficient ethylene glycol concentration — below minimum 30%
Check: Measure concentration on-site with refractometer within 10 minutes — add glycol immediately if below 30%. Freeze point conversion: EG 30%→-16°C, 35%→-20°C, 40%→-24°C
What to do: Inject glycol concentrate directly to adjust concentration — design freeze point = region's lowest temperature minus 5°C safety margin. Re-measure with refractometer after top-up
Over-dilution from excess makeup water — concentration not readjusted after refilling
Check: Check leak history and verify refractometer measurement records after each makeup water addition. Measure on-site immediately if not in regular inspection records
What to do: Establish makeup water protocol: re-measure with refractometer immediately after top-up → add concentrate to correct if below target. Set concentration-linked control if automatic makeup system installed
Glycol degradation (oxidation) — pH below 7.0 or browning indicates increased corrosivity
Check: Measure pH on-site with pH strips or meter — replace or add corrosion inhibitor if pH outside 7.0–9.0 range. Visually inspect glycol for brown discoloration
What to do: Add corrosion inhibitor or fully replace solution if pH below 7.0. Before cold snap: maintain circulation pump at low speed before shutdown or activate electric freeze-protection heaters
Refractometer is a must-have field tool. EG 30% = -16°C freeze point. Set 5°C below your region's lowest temperature. Re-measure every time you top up — unmeasured concentration is the main cause of freeze accidents.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)