CO2 Dry Ice Blockage in Expansion Valve (Operation Below Triple Point)
Likely causes
Low-pressure cut-out set too low (below 6 bar) — CO2 solidifies to dry ice below triple point (-56.6°C, 5.2 bar)
Check: Check low-pressure cut-out setpoint — if below 7–8 bar, adjust immediately. Check controller low-pressure trip history
What to do: Raise low-pressure cut-out to 7–8 bar to maintain triple-point safety margin. If dry ice blockage confirmed: run hot-gas defrost for 10 min (hot gas ~40°C) → blockage clears, then restart
Expansion valve over-opening → evaporator pressure drops sharply → below triple point
Check: Check EEV minimum opening limit (electronic expansion valve minimum step ≥20). Review evaporator pressure log
What to do: Set EEV minimum opening limit to step ≥20. Test solenoid valve for leakage when closed (observe pressure hold for 30 min)
Moisture present — below 5°C, water ice and dry ice form simultaneously
Check: Check sight glass moisture indicator. Perform acid test
What to do: After acid test, replace filter drier with CO2-compatible molecular sieve type. Recover all refrigerant → flush with dry nitrogen → evacuate → recharge
CO2 solidifies to dry ice instantly below the triple point (-56.6°C, 5.2 bar). Always set low-pressure alarm above 7 bar. Run hot-gas defrost for 10 min immediately upon low-pressure trip, then diagnose cause.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Cold Storage / Freezer Temperature Rising
- Walk-in Evaporator Frost Buildup / Defrost Failure
- Cold Storage Compressor Failure to Start / Overload
- Moisture Contamination in Cold Storage System
- Freezer Floor Heating Cable Break → Floor Frost Heave
- Door Gasket Hardening & Shrinkage → Cold Air Leakage (External Condensation Worsening)