Cooling Water Temperature Rise (Water-Cooled)

Likely causes

Cooling tower fan faulty

Check: Check cooling tower fan current and rotation

What to do: Check cooling tower fan current and rotation → Inspect and clean fill media if blocked → Measure cooling water inlet temperature (design: ≤32°C) → Check spray nozzles on cooling tower for blockage → In hot summer conditions, consider supplemental cooling water cooling measures

Fill media clogged or aged

Check: Inspect and clean fill media if blocked

What to do: Inspect and clean fill media if blocked → Measure cooling water inlet temperature (design: ≤32°C) → Check spray nozzles on cooling tower for blockage → In hot summer conditions, consider supplemental cooling water cooling measures

Reduced cooling performance in hot humid summer conditions

Check: Measure cooling water inlet temperature (design: ≤32°C)

What to do: Measure cooling water inlet temperature (design: ≤32°C) → Check spray nozzles on cooling tower for blockage → In hot summer conditions, consider supplemental cooling water cooling measures

Field tip

Flow is normal but the cooling water temperature itself is too high. Inspect the cooling tower and water circuit.