R-Pro › Field cases › Chillers
Double-Pipe Condenser Refrigerant/Water Cross-Leakage (Pressure Test Identification)
Likely causes
Pinhole corrosion in inner tube
Check: refrigerant (high pressure, 1.5~2.5 MPa) leaks into water side
What to do: Determine leak direction: pressurize refrigerant side with N2 to 1.2 MPa, isolate water side → if water-side pressure rises, leak is from refrigerant to water
Fatigue cracking at U-bend hairpin weld
Check: bidirectional refrigerant/water mixing
What to do: Check reverse direction: pressurize water side to 0.6 MPa + monitor refrigerant-side pressure gauge → confirm water-to-refrigerant direction
Water-side pressure exceeds refrigerant-side pressure (pump overpressure > 0.8 MPa)
Check: moisture infiltrates refrigerant circuit
What to do: Locate leak: inject N2 into each loop separately + bubble test (focus on hairpin weld joints)
Scale on inner tube outer surface reduces heat transfer
Check: localized overheating → tube wall degradation
What to do: Replace inner tube: use same specification or SUS316L stainless inner tube; perform X-ray inspection of welds before use
Vibration/pulsation loosens fittings
Check: gap leakage
What to do: Install water-side pressure regulator: limit pump outlet to ≤ 0.5 MPa to prevent pressure reversal into refrigerant circuit
Always pressurize the lower-pressure side first before start-up — pressure reversal rapidly expands pinholes.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)