R-Pro › Field cases › Cooling towers

Drift Eliminator Damage

Likely causes

PVC panels brittle and cracked from long-term UV and ozone exposure

Check: Visually inspect all panels — check for cracks, dislodgment, and deformation; check water droplet carryover around tower (excessive drift = replace panels)

What to do: Immediately replace cracked/dislodged/deformed panels (same-spec PVC) → inspect all retaining clips and install missing ones → recommend annual removal, inspection, cleaning, and reinstallation of all panels

Panels damaged by direct high-pressure wash or excessive scale causing increased airflow resistance and damage

Check: Check cleaning method — whether high-pressure nozzle aimed perpendicularly at panels; measure scale thickness and check for increased airflow resistance

What to do: Replace damaged panels → set cleaning rules: maintain high-pressure washer at least 30 cm away, never aim perpendicularly → descale: spray 5% HCl, wait 10 min, rinse with low-pressure water (wear protective gloves)

Field tip

Damaged drift eliminators increase water droplet carryover, raising both building corrosion and Legionella transmission risks. Replace immediately upon discovery.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases