R-Pro › Field cases › Freezers & ultra-low temperature

DX Evaporator Multi-circuit Maldistribution — Superheat Imbalance Between Circuits

Likely causes

Distributor nozzle clogging or partial blockage of some holes

Check: Inspect with instruments or visually

What to do: Measure superheat at each circuit outlet: compare outlet pipe temperatures; normal 5–8 K, imbalance if deviation ≥ 3 K

Non-uniform two-phase refrigerant velocity

Check: eccentric inlet header installation

What to do: Remove distributor and clean each nozzle hole visually and with wire; purge with nitrogen reverse pressure if debris found

Gravity bias due to coil height/length differences between circuits

Check: Inspect with instruments or visually

What to do: Check TXV opening — readjust superheat setpoint to 5–6 K and restore overall flow first

Insufficient TXV opening

Check: overall refrigerant flow deficiency

What to do: Verify refrigerant charge — no bubbles in sight glass + subcooling 5–8 K, then top up in small increments

Excessive gas entrainment at distributor inlet due to refrigerant shortage

Check: Inspect with instruments or visually

What to do: Check distributor inlet pipe inclination and reinstall level (maintain vertical inlet flow into header)

Field tip

To quickly identify unbalanced circuits, scan each outlet header pipe at 10 mm intervals with a non-contact thermometer — imbalanced circuits can be pinpointed within 30 seconds.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases