R-Pro › Field cases › Components

EEV Stepper Motor Coil Open Circuit — Resistance Test 40–80Ω

Likely causes

Coil winding internal open circuit — vibration, overcurrent, or deterioration

Check: Measure coil resistance with multimeter (connector disconnected): A1-A2 and B1-B2 each 40–80Ω; OL confirms open circuit

What to do: If model allows separate coil replacement → replace coil only; otherwise → replace full EEV → run Reset/Initialize on controller after replacement

Connector pin corrosion or increased contact resistance

Check: If coil resistance is normal (40–80Ω) → connector pin pull test + contact resistance below 2Ω

What to do: Clean contacts with pin cleaner, re-measure contact resistance → if no improvement, replace connector

EEV driver board output stage failure

Check: Coil resistance normal + connector normal → check EEV driver board for 5V control signal output with oscilloscope

What to do: Check supply voltage and controller comms line before replacing driver board → initialize EEV after board replacement

Field tip

Always measure coil resistance with connector disconnected — measuring while connected to driver board gives false readings

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases