R-Pro › Field cases › Chillers

Heat Recovery Circuit Switching Failure → Waste Heat Loss

Likely causes

4-way switchover solenoid valve (HR valve) coil burned out

Check: unable to switch circuit when heat recovery mode is requested

What to do: Measure HR solenoid valve coil resistance (normal 15–30 Ω): replace coil or valve if burned

Insufficient cooling water flow through heat recovery heat exchanger (desuperheater)

Check: flow switch failed or pump stopped

What to do: Check cooling water flow: verify heat exchanger inlet/outlet temperature difference (normal 5–8 °C); if flow is low, check pump and piping blockages

Controller heat recovery interlock conditions not met

Check: compressor discharge temperature or demand signal not fed in

What to do: Force-activate HR mode from controller service menu: output HR solenoid ON → listen for valve click

Refrigerant leak in HR circuit causing pressure imbalance

Check: solenoid valve cannot open

What to do: Check HR circuit for leaks with low-side gauge: after shutdown and equalization, HR line and main line pressures must match

Demand signal wire break from heat recovery load (hot water tank, AHU preheat, etc.)

Check: controller always stays in non-recovery mode

What to do: Continuity test on demand signal wiring: confirm resistance ≤1 kΩ

Field tip

When heat recovery is active, condenser fan speed should decrease — if the fan keeps running at full speed, HR is not actually working.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases