High Pressure Rise from Condenser Fan Failure
Likely causes
Fan motor winding open or burned out
Check: Confirm voltage is applied to fan motor terminals
What to do: Confirm voltage is applied to fan motor terminals → Measure capacitor capacitance (within ±10% of rated) → Try to turn fan blade by hand (seized = bearing failure or foreign object) → Measure motor winding resistance (open circuit = ∞) → Replace fan motor or capacitor with same specification
Start capacitor faulty
Check: Measure capacitor capacitance (within ±10% of rated)
What to do: Measure capacitor capacitance (within ±10% of rated) → Try to turn fan blade by hand (seized = bearing failure or foreign object) → Measure motor winding resistance (open circuit = ∞) → Replace fan motor or capacitor with same specification
Fan blade blocked by foreign object causing overload stop
Check: Try to turn fan blade by hand (seized = bearing failure or foreign object)
What to do: Try to turn fan blade by hand (seized = bearing failure or foreign object) → Measure motor winding resistance (open circuit = ∞) → Replace fan motor or capacitor with same specification
The condenser fan is not operating, preventing heat rejection. Replace the fan motor or capacitor. Always cut power before inspecting the fan motor. The fan may restart unexpectedly.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)