R-Pro › Field cases › Chillers

High Pressure Rise from Insufficient Cooling Water Flow (Water-Cooled)

Likely causes

Cooling water pump faulty or undersized

Check: Measure cooling water inlet-outlet temperature difference (normal 5–8°C; high = insufficient flow)

What to do: Measure cooling water inlet-outlet temperature difference (normal 5–8°C; high = insufficient flow) → Measure pump running current and discharge pressure → Check valve opening → Inspect cooling tower fan and fill media → Check chemical cleaning cycle (typically once a year)

Flow path narrowed by scale/slime in cooling water piping

Check: Measure pump running current and discharge pressure

What to do: Measure pump running current and discharge pressure → Check valve opening → Inspect cooling tower fan and fill media → Check chemical cleaning cycle (typically once a year)

Cooling water valve not fully open or excessive pressure drop

Check: Check valve opening

What to do: Check valve opening → Inspect cooling tower fan and fill media → Check chemical cleaning cycle (typically once a year)

Cooling tower degradation raising cooling water temperature

Check: Inspect cooling tower fan and fill media

What to do: Inspect cooling tower fan and fill media → Check chemical cleaning cycle (typically once a year)

Field tip

Insufficient cooling water flow is raising condensing temperature. Check pump, piping, and valves. Condensing performance drops sharply when cooling water temperature exceeds 32°C. Improve cooling tower maintenance.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases