High Pressure Rise from Non-condensable Gas (Air) in Circuit
Likely causes
Refrigerant charged without adequate evacuation
Check: Diagnosis: if high-side pressure is clearly above saturated pressure for the condensing temp, air is suspected
What to do: Diagnosis: if high-side pressure is clearly above saturated pressure for the condensing temp, air is suspected → Recover all refrigerant → Evacuate to ≤500 μm Hg (minimum 1 hour) → Hold vacuum for 30 minutes (vacuum loss = repair leak first) → Recharge refrigerant by weight
System opened and re-sealed without recovering refrigerant
Check: Recover all refrigerant
What to do: Recover all refrigerant → Evacuate to ≤500 μm Hg (minimum 1 hour) → Hold vacuum for 30 minutes (vacuum loss = repair leak first) → Recharge refrigerant by weight
Air back-leaked through service valve core
Check: Evacuate to ≤500 μm Hg (minimum 1 hour)
What to do: Evacuate to ≤500 μm Hg (minimum 1 hour) → Hold vacuum for 30 minutes (vacuum loss = repair leak first) → Recharge refrigerant by weight
Air in the circuit is adding non-condensable pressure. Perform an air purge. Air contamination raises condensing pressure abnormally, causing repeated high-pressure switch trips and compressor burnout.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)