High Pressure Rise from Refrigerant Overcharge
Likely causes
Overcharge during service without weighing
Check: Measure subcooling: condenser outlet temp − condensing sat. temp (>10°C = overcharge suspected)
What to do: Measure subcooling: condenser outlet temp − condensing sat. temp (>10°C = overcharge suspected) → Recover excess refrigerant with recovery equipment → Recover in small steps until subcooling reaches 5–8°C → Also verify superheat simultaneously (5–10°C range)
Repeated refrigerant additions without tracking previous charges
Check: Recover excess refrigerant with recovery equipment
What to do: Recover excess refrigerant with recovery equipment → Recover in small steps until subcooling reaches 5–8°C → Also verify superheat simultaneously (5–10°C range)
Refrigerant overcharge floods the condenser with liquid, raising high-side pressure. Recover excess refrigerant. Do not release refrigerant to atmosphere. Always use recovery equipment.