R-Pro › Field cases › Chillers

High Pressure Rise from Refrigerant Overcharge

Likely causes

Overcharge during service without weighing

Check: Measure subcooling: condenser outlet temp − condensing sat. temp (>10°C = overcharge suspected)

What to do: Measure subcooling: condenser outlet temp − condensing sat. temp (>10°C = overcharge suspected) → Recover excess refrigerant with recovery equipment → Recover in small steps until subcooling reaches 5–8°C → Also verify superheat simultaneously (5–10°C range)

Repeated refrigerant additions without tracking previous charges

Check: Recover excess refrigerant with recovery equipment

What to do: Recover excess refrigerant with recovery equipment → Recover in small steps until subcooling reaches 5–8°C → Also verify superheat simultaneously (5–10°C range)

Field tip

Refrigerant overcharge floods the condenser with liquid, raising high-side pressure. Recover excess refrigerant. Do not release refrigerant to atmosphere. Always use recovery equipment.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases