Indoor Unit Blower Bearing Wear → Characteristic Frequency Peak in Spectrum Analysis

Likely causes

Bearing lubrication shortage (grease depleted) → BPFO/BPFI frequency peaks

Check: Press stethoscope rod (screwdriver handle) against bearing area and listen — 'grinding' sensation indicates replacement; check for abnormal peaks in 1 kHz, 3 kHz, 5 kHz bands with smartphone noise app

What to do: Check for grease nipple — replenish with NLGI Grade 2 grease if accessible; if noise persists or recurs within 3 days, replace bearing with equivalent (manufacturer number); use dedicated tool during replacement (no hammering) — verify shaft squareness and interference fit

Indoor condensate water ingress — accelerated bearing corrosion

Check: Check for condensate traces around bearing (rust, white residue); inspect drain pan (blockage, cracks); identify poor insulation areas

What to do: Block condensate water ingress path (clean and repair drain pan, reinforce insulation); use waterproof grease when replacing bearing; apply anti-corrosion treatment to bearing cover

Field tip

Bearing noise can be judged in 10 seconds with a stethoscope rod — if it recurs within 3 days after grease replenishment, replace immediately.