Low Chilled Water Flow → Evaporator Freeze Protection Trip
Likely causes
Evaporator water-side strainer clogged — flow drops sharply when differential pressure exceeds 50 kPa
Check: Measure strainer differential pressure — clean immediately if >50 kPa. Evaporator ΔT >8°C confirms insufficient flow (normal 5–8°C)
What to do: Clean strainer (recommend periodic cleaning every 6 months) → verify flow recovery after cleaning → confirm ΔT returns to 5–8°C
Chilled water pump impeller wear or air entrainment
Check: Measure pump current — if more than 15% below rated, suspect impeller wear or air entrainment. Check pump outlet pressure
What to do: Open high-point air vents to remove air → replace impeller if flow does not recover. Install automatic air vent if air pockets recur
Motorized valve actuator malfunction — opening stuck below 30%
Check: Manually verify motorized valve opens to 100% — if opens manually, actuator is faulty. Measure valve control signal (4–20 mA) to confirm signal is normal
What to do: Replace actuator. Check for wire breakage and poor connections, then reconnect
Evaporator ΔT below 6°C = excessive flow or sudden load drop; above 8°C = insufficient flow. Check both thresholds on-site immediately. Strainer ΔP 50 kPa = clean immediately.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)