Multiple Chiller Sequence Control Imbalance — Operating Hours Rotation Failure
Likely causes
BMS lacks rotation logic based on accumulated operating hours
Check: Check each chiller accumulated operating hours — if deviation exceeds 200 hours, rotation not being performed. Verify in BMS sequence logic whether chiller #1 is always set as fixed lead unit
What to do: Implement automatic rotation logic in BMS based on accumulated hours — auto-switch lead unit when difference exceeds 200 hours. Without BMS, manually switch lead unit monthly and reset operating hour records
Chilled water setpoint temperature variance between chillers — parallel load imbalance
Check: Measure actual supply temperature of each chiller — if there is variance like #1 at 5°C and #2 at 6°C, load concentrates on the lower-temperature chiller. Check header branch valve openings — verify all chiller supply and return valves at 100% opening
What to do: Unify chilled water supply temperature setpoint across all chillers — keep supply temp variance within ±0.5°C during parallel operation. Reset sequence thresholds: load ≥75% → start next chiller; load ≤45% → stop one unit (30% hysteresis band). After rotation, confirm previous unit current = 0 A before proceeding
Operating hour difference ≥200 hours = rotate immediately. Without BMS, manually switch lead unit monthly to prevent uneven wear.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)