R-Pro › Field cases › Chillers

Multiple Chiller Sequence Control Imbalance — Operating Hours Rotation Failure

Likely causes

BMS lacks rotation logic based on accumulated operating hours

Check: Check each chiller accumulated operating hours — if deviation exceeds 200 hours, rotation not being performed. Verify in BMS sequence logic whether chiller #1 is always set as fixed lead unit

What to do: Implement automatic rotation logic in BMS based on accumulated hours — auto-switch lead unit when difference exceeds 200 hours. Without BMS, manually switch lead unit monthly and reset operating hour records

Chilled water setpoint temperature variance between chillers — parallel load imbalance

Check: Measure actual supply temperature of each chiller — if there is variance like #1 at 5°C and #2 at 6°C, load concentrates on the lower-temperature chiller. Check header branch valve openings — verify all chiller supply and return valves at 100% opening

What to do: Unify chilled water supply temperature setpoint across all chillers — keep supply temp variance within ±0.5°C during parallel operation. Reset sequence thresholds: load ≥75% → start next chiller; load ≤45% → stop one unit (30% hysteresis band). After rotation, confirm previous unit current = 0 A before proceeding

Field tip

Operating hour difference ≥200 hours = rotate immediately. Without BMS, manually switch lead unit monthly to prevent uneven wear.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases