Oil Separator Heater Open Circuit — Liquid Slugging at Startup

Likely causes

Heater resistance wire open circuit — premature failure from repeated high-temperature exposure (service life 3–5 years)

Check: Measure heater resistance with multimeter — OL (infinite) confirms open circuit; normal heater 50–200 Ω (varies by capacity); also verify 220 V supply with terminals disconnected

What to do: Shut off oil return line and replace heater (external heater band type → replace band only, no separator disassembly needed) → verify thermostat set to 20–40°C

Refrigerant dissolves into oil during prolonged low-temperature storage — liquid slugging at startup

Check: Before startup, check for oil foaming or crankcase abnormal noise; verify heater non-operation history

What to do: Ambient below 10°C: minimum 4 hours pre-heat; below 0°C: minimum 8 hours; start after crankcase heater warm-up → if liquid slugging occurs, stop immediately → replace oil if heavily diluted before restarting

Field tip

Always verify heater operation before winter startup — resistance check with multimeter takes only 30 seconds; a failed heater leading to compressor damage means repair costs 100x higher