Plate Heat Exchanger Leak — Refrigerant and Chilled Water Cross-contamination
Likely causes
Micro-cracks in brazed plates
Check: metal fatigue from repeated thermal shock (start/stop cycles)
What to do: Cross-check pressures on refrigerant and chilled water sides — look for refrigerant bubbles or oil in chilled water circuit to determine contamination direction
Degraded/hardened gaskets in gasketed plate type
Check: loss of sealing
What to do: Pinpoint leak location in brazed plate — drain chilled water, pressurize refrigerant side with nitrogen (0.7 MPa), and detect bubbles on plate surface
Corrosion of plate material from excessive acidic descaling chemicals on chilled water side
Check: Inspect with instruments or visually
What to do: Replace entire unit if brazed plate is damaged (single-plate repair not feasible; re-brazing is temporary and typically recurs within 6 months)
Abnormal pressure rise on refrigerant side
Check: cracks from instantaneous overpressure due to repeated high-pressure trips
What to do: For gasketed type leaks — re-torque all bolts to manufacturer spec uniformly, replace full gasket set, and reassemble
Non-uniform bolt torque causing plate deformation
Check: localized leaks in gasketed type
What to do: After descaling chilled water side, measure pH and chloride level; readjust water treatment chemical concentration
Early sign of plate cross-contamination: refrigeration oil smell (rotten egg or mineral oil odor) in chilled water piping or oil film on chilled water tank surface — inspect immediately.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Cold Storage / Freezer Temperature Rising
- Walk-in Evaporator Frost Buildup / Defrost Failure
- Cold Storage Compressor Failure to Start / Overload
- Moisture Contamination in Cold Storage System
- Freezer Floor Heating Cable Break → Floor Frost Heave
- Door Gasket Hardening & Shrinkage → Cold Air Leakage (External Condensation Worsening)