Poor Heat Transfer from Scale Buildup on Cooling Tubes (Water-Cooled)

Likely causes

Calcium/magnesium scale from poor water quality management

Check: Measure cooling tube inlet-outlet temp diff (scale suspected if >2°C above design)

What to do: Measure cooling tube inlet-outlet temp diff (scale suspected if >2°C above design) → Perform chemical descaling (acid wash) or mechanical descaling (brush cleaning) → After descaling, analyze cooling water quality (maintain pH 7–8) → Consider installing automatic water treatment chemical dosing → Perform annual descaling thereafter

Cooling water pH not managed

Check: Perform chemical descaling (acid wash) or mechanical descaling (brush cleaning)

What to do: Perform chemical descaling (acid wash) or mechanical descaling (brush cleaning) → After descaling, analyze cooling water quality (maintain pH 7–8) → Consider installing automatic water treatment chemical dosing → Perform annual descaling thereafter

Descaling schedule not followed

Check: After descaling, analyze cooling water quality (maintain pH 7–8)

What to do: After descaling, analyze cooling water quality (maintain pH 7–8) → Consider installing automatic water treatment chemical dosing → Perform annual descaling thereafter

Field tip

Scale on cooling tube walls is impeding heat transfer, raising condensing temperature and high-side pressure. Descale the tubes. Close refrigerant valves during acid wash to prevent cleaning solution from entering the refrigerant circuit.