R-Pro › Field cases › Chillers
Primary/Secondary Pump Decoupler Reverse Flow — Bypass Piping Design Error
Likely causes
Decoupler straight pipe length under 6D causes reverse flow
Check: Measure decoupler pipe length — verify ≥6× pipe diameter (6D) of straight pipe. Install temporary thermometers at both ends of decoupler → if return-side temp is 0.5°C+ higher than supply side, reverse flow confirmed
What to do: Secure straight pipe ≥6D — extend pipe if existing is too short. If immediate fix not possible, add one spring check valve to decoupler → increase primary pump speed so primary flow (LPM) ≥ secondary flow
Primary flow < secondary flow — excess reverses through decoupler
Check: Measure primary and secondary flow separately (ultrasonic flow meter or BMS display). If primary flow < secondary flow, reverse flow is occurring. Supply temperature rise (chilled water 7°C → 8.5°C+) suspects warm return water mixing due to reverse flow
What to do: Increase primary pump speed (raise inverter frequency 3~5 Hz) → recheck flow measurement. Re-adjust secondary loop balancing valves — bring each loop flow variance within ±10%. If no flow meter, use clamp-type ultrasonic meter for temporary measurement then plan permanent installation
Poor secondary loop balancing — flow variance between loops exceeds 30%
Check: Check AHU or FCU inlet/outlet temperature difference — larger ΔT variance indicates flow imbalance. If no pressure-independent control valves (PICV), determine current balancing valve opening status on each loop
What to do: Sequentially adjust each loop balancing valve — use the farthest loop as reference (100% open) and proportionally adjust remaining loops. After adjustment, re-measure entire system to confirm no total flow reduction. Long-term: recommend replacing with PICV (pressure-independent control valves)
If decoupler return-side temperature is even 0.5°C above supply side, reverse flow is occurring — immediately raise primary pump speed to correct.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Chiller Low Pressure (LP) Trip — Low Refrigerant or Expansion Valve Fault
- Unable to Reach Process Temperature — Chiller Setpoint Not Achieved
- Compressor Unresponsive Despite Start Command from Control Panel
- Oil Pressure Trip / Low Oil Level
- Water-Cooled Condenser Tube Fouling (ΔT >5°C)
- Air-Cooled Chiller High-Temperature Trip (Ambient >45°C)