Screw Chiller Oil Filter Clog (ΔP >0.15 MPa, Replace Every 2,000 Hours)

Likely causes

Over 2,000 operating hours without replacement — sludge and metal particles cause ΔP increase

Check: Check oil filter ΔP daily — schedule replacement at 0.10 MPa, replace immediately if >0.15 MPa. Confirm cumulative hours from hour meter

What to do: Replace oil simultaneously when replacing filter → after installing new filter, remove air via purge valve → top up oil to midpoint of sight glass

Oil degradation (TAN >0.5 mgKOH/g) — oxidation sludge formation

Check: Request oil sample analysis (every 6 months recommended): TAN, viscosity, metal content. Separately inspect bearing wear if excessive metal particles

What to do: Replace all oil + replace filter. If metal particles abnormal, consider early bearing replacement — replacing filter alone does not solve the root cause

Refrigerant liquid mixing into oil — oil dilution and accelerated contamination

Check: Check for oil foaming and abnormal noise immediately after startup. Verify crankcase heater operation (failure is a cause of refrigerant migration)

What to do: Replace/repair crankcase heater. Establish 2+ hour pre-start heater operation procedure. Replace oil + filter

Field tip

Oil filter ΔP 0.15 MPa = immediate replacement threshold. Proactive replacement every 2,000 hours can more than double compressor bearing life. Always replace oil together when replacing filter.