Scroll Internal Liquid Slug — Tip Fracture and Scroll Volute Crack
Likely causes
TXV/EEV superheat below 3°C — liquid refrigerant enters suction, strikes compression chamber directly
Check: Immediately after startup: metallic hammering noise + current spikes to 150~200% rated then immediate overload trip. Measure superheat — must be ≥5°C for normal operation
What to do: Tighten TXV screw to achieve 5~8°C superheat (for EEV, enter target SH in controller) → establish SOP: fans first, wait 3 min, then start compressor → disassemble compressor: inspect tip fractures — if damaged, replace entire scroll assembly
Metal debris from fractured tips contaminates entire refrigerant circuit
Check: Take oil sample: visually check for metal particles + magnet test. When replacing filter drier, check screen for contamination or blockage
What to do: Full system flush (recover all refrigerant → circulate flushing agent → recover again) → replace all filter driers → replace compressor → confirm vacuum ≤500μm before recharging
Knocking at startup + immediate trip = liquid slug confirmed. Metal debris circulating through the system causes secondary damage to EEV, expansion valves, and solenoids. Oil sampling before restart is mandatory.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Liquid Refrigerant Entering Compressor (Flooded Start / Liquid Slugging)
- Compressor Motor Burnout / Ground Fault
- High Compressor Discharge Temperature (>107°C scroll, >120°C recip)
- Scroll Compressor Reverse Rotation — 3-Phase Miswiring
- Scroll Tip Seal Wear — Volumetric Efficiency Loss and Reduced Cooling Capacity
- Scroll Poppet Valve Fails to Close — Reverse Rotation Noise After Shutdown