Sight Glass Bubble Formation
Likely causes
Low refrigerant charge — system refrigerant reduced due to leaks (most common cause)
Check: First check for leaks with electronic detector or soap bubbles → if no leak, check drier ΔT and subcooling
What to do: Repair leak → evacuate 30 min → recharge to specified weight (use scale) → verify bubbles disappear after operation
Drier clogging causing pressure drop after drier → flash gas generation
Check: Measure drier inlet/outlet temperature — ΔT ≥ 3°C indicates drier clog
What to do: Replace drier → evacuate → recharge → verify bubbles disappear
Minor bubbles normal with blended refrigerants (e.g., R-404A, R-407C) — avoid misdiagnosis
Check: Identify refrigerant type — R-404A/R-407C minor bubbles are normal. Confirm no leak and normal ΔT before concluding
What to do: No repair needed for minor bubbles in blended refrigerants. Do not overcharge based on misdiagnosis
Sight glass bubbles do NOT always mean low charge. Check drier ΔT and subcooling first. Minor bubbles are normal with blended refrigerants.