R-Pro › Field cases › Components

Sight Glass Bubble Formation

Likely causes

Low refrigerant charge — system refrigerant reduced due to leaks (most common cause)

Check: First check for leaks with electronic detector or soap bubbles → if no leak, check drier ΔT and subcooling

What to do: Repair leak → evacuate 30 min → recharge to specified weight (use scale) → verify bubbles disappear after operation

Drier clogging causing pressure drop after drier → flash gas generation

Check: Measure drier inlet/outlet temperature — ΔT ≥ 3°C indicates drier clog

What to do: Replace drier → evacuate → recharge → verify bubbles disappear

Minor bubbles normal with blended refrigerants (e.g., R-404A, R-407C) — avoid misdiagnosis

Check: Identify refrigerant type — R-404A/R-407C minor bubbles are normal. Confirm no leak and normal ΔT before concluding

What to do: No repair needed for minor bubbles in blended refrigerants. Do not overcharge based on misdiagnosis

Field tip

Sight glass bubbles do NOT always mean low charge. Check drier ΔT and subcooling first. Minor bubbles are normal with blended refrigerants.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases