Subcooling Insufficient (<3°C) → Flash Gas in Liquid Line → TXV Hunting

Likely causes

Refrigerant shortage → insufficient refrigerant in condenser → subcooling below target

Check: Check liquid-line sight glass for bubbles + measure subcooling (target 5–8°C)

What to do: Leak check → repair leak → evacuate 30 min → recharge to spec

Excessive pressure drop in liquid line — oversized run or filter-drier clogged

Check: Measure filter-drier inlet/outlet temperature difference — >1°C indicates clogged

What to do: Replace filter-drier → evacuate then recharge

Receiver absent or undersized → low liquid level → unstable subcooling

Check: Check receiver sight glass for bubbles or liquid level below 1/4

What to do: Add refrigerant until sight glass clears and subcooling reaches 5–8°C

Field tip

Bubbles in sight glass confirm subcooling <3°C — always find the leak before adding refrigerant.