R-Pro › Field cases › Components

Twin-Rotary Phase Synchronization Failure → Abnormal Vibration Increase

Likely causes

Wear or loss of dowel pin maintaining 180° phase angle between upper and lower cylinders

Check: Measure compressor housing vibration with vibration meter — normal < 2.8 mm/s (RMS); stop immediately if > 4.5 mm/s. Disassemble and inspect dowel pin: verify diameter tolerance within ±0.01 mm

What to do: Replace worn dowel pins with new → reassemble upper/lower cylinders with uniform torque 15–20 N·m using torque wrench → replace oil with specified grade (VG32–46) → re-measure vibration after repair (target ≤ 2.0 mm/s)

Crankshaft eccentric journal wear → unequal stroke between upper and lower rotors

Check: Measure crankshaft eccentric journal roundness with micrometer — replace if deviation > 0.02 mm. In vibration frequency analysis, strong 2× rotational frequency component indicates stroke imbalance

What to do: Replace crankshaft → verify new part eccentric journal roundness before assembly → measure vibration after reassembly: confirm ≤ 2.0 mm/s. If still elevated, inspect and adjust balance weights

High-viscosity oil (VG68+) or assembly defect (uneven bolt torque)

Check: Check oil viscosity: verify VG grade from label or viscometer — replace immediately if VG68 or higher. Review recent maintenance history: look up cylinder bolt torque records

What to do: Replace all oil with specified viscosity (VG32–46) → verify cylinder bolt seating and re-torque to 15–20 N·m with torque wrench → re-measure vibration: target ≤ 2.8 mm/s

Field tip

Twin-rotary vibration: do not continue operating in 2.8–4.5 mm/s range — recommend preventive disassembly before 4.5 mm/s alarm. Without vibration meter, a screwdriver-handle stethoscope is more accurate than hand-feel.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases