TXV Superheat Maladjustment — Hunting or Liquid Slugging
Likely causes
Spring too loose — liquid refrigerant enters compressor (liquid slugging)
Check: Measure actual superheat: clamp thermometer on suction line + low-pressure gauge; superheat = suction pipe temp − evaporating saturation temp; superheat below 3°C indicates liquid slugging risk
What to do: Adjust TXV screw clockwise (CW) 1/4 turn at a time → wait 15 min → re-measure; target superheat 4–8°C (refrigeration) or 5–10°C (air conditioning)
Spring over-tightened — restricted refrigerant flow reduces capacity
Check: Superheat above 10°C + reduced capacity → suspect over-tight spring; suction pressure lower than normal and no frost on suction line
What to do: Adjust TXV screw counterclockwise (CCW) 1/4 turn at a time → wait 15 min → re-measure; stop adjustment when superheat reaches target range
Bulb improperly positioned — false superheat signal
Check: Check if bulb is mounted at frost/condensation point or on underside of suction line → confirm 12 o'clock position and insulation contact
What to do: Remount bulb at 12 o'clock → fully wrap with insulation → recheck after 15 min to confirm hunting resolved
After each 1/4-turn TXV adjustment, always wait at least 15 minutes — multiple rapid turns cause excessive superheat and capacity loss
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Liquid Refrigerant Entering Compressor (Flooded Start / Liquid Slugging)
- Compressor Motor Burnout / Ground Fault
- High Compressor Discharge Temperature (>107°C scroll, >120°C recip)
- Scroll Compressor Reverse Rotation — 3-Phase Miswiring
- Scroll Tip Seal Wear — Volumetric Efficiency Loss and Reduced Cooling Capacity
- Scroll Poppet Valve Fails to Close — Reverse Rotation Noise After Shutdown