R-Pro › Field cases › Chillers

U-Bend Fatigue Cracking from Thermal Stress and Freezing

Likely causes

Repeated start/stop cycles with refrigerant ΔT > 50°C

Check: copper U-bend expansion/contraction cycles → fatigue crack

What to do: Confirm crack: apply liquid penetrant test (PT) on U-bend surface or pressurize with N2 at 0.8 MPa and bubble-test to locate crack

Repeated freeze-thaw cycles (ice expansion ~9%)

Check: plastic deformation accumulates in U-bend → eventual cracking

What to do: Replace cracked U-bend: use deoxidized copper (TP2, C1220T), ensure bend radius R ≥ 1.5D, reconfirm with PT after brazing

Insufficient bend radius (R < 1.5D)

Check: stress concentration → accelerated cracking

What to do: Absorb thermal expansion: install expansion loop or U-shape compensation tube in straight section → self-absorbs thermal growth

Poor brazing

Check: capillary voids → crack initiation site

What to do: Install vibration clamps: fix clamp within 150 mm of U-bend (isolates vibration transmission)

Missing vibration clamps

Check: resonance causes repeated bending load on U-bend

What to do: Prevention: during nightly shutdown, recover refrigerant from circuit + open drain valve to remove residual water

Field tip

After U-bend replacement, check braze quality: uniform silver sheen on copper surface is good; black oxide or bubble marks require rework.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases