R-Pro › Field cases › VRF systems

EEV Stuck — Reduced Cooling/Heating Capacity

Likely causes

EEV coil open circuit or resistance failure — opening degree uncontrollable

Check: Remove EEV coil and measure resistance: normal 40–80Ω — check for open circuit (infinity) or short (0Ω)

What to do: Replace faulty coil → send EEV manual open command and verify valve movement → confirm refrigerant pressure normalization

Foreign object lodged in EEV body — mechanical valve seizure

Check: Recover refrigerant, disassemble EEV — visually inspect valve seat for debris, rust, sludge

What to do: Remove debris and clean → replace EEV assembly if severe → nitrogen pressure test for leaks after replacement

Moisture ingress in refrigerant — EEV internal icing causing seizure

Check: After refrigerant recovery, use acid/moisture test kit — moisture above 100ppm indicates contamination → check dryer filter saturation

What to do: Replace dryer filter → vacuum dry for ≥72 hours → charge with fresh refrigerant → verify EEV normal operation

Field tip

If EEV coil resistance deviates from 40–80Ω, replace coil immediately — suspect coil before control board.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases