P/Q Communication Wire Open/Short Circuit — Indoor Unit Communication Error
Likely causes
P/Q wiring connector poor connection or terminal under-torque
Check: Check torque of each P/Q terminal block connection: normal 0.5–0.8 N·m → visually inspect terminals for oxidation/corrosion
What to do: Sand oxidized terminals and reattach → re-tighten to specified torque (0.5–0.8 N·m) → clear communication error codes and restart
Termination resistor not installed — frequent errors from signal reflection
Check: Measure resistance between P-Q at the farthest indoor unit terminal block: normal 120Ω — verify termination resistor installation
What to do: Install 120Ω termination resistor at P-Q terminals of the farthest indoor unit → re-check communication error frequency
P/Q wiring total length exceeds 500m — signal attenuation
Check: Calculate total P/Q wiring length → check if exceeds 500m → measure P-Q voltage at farthest indoor unit (normal DC 14–16V)
What to do: Install additional repeater → review wiring route to reduce total length → consider adding outdoor unit or splitting the system
Checking P/Q terminal resistance of 120Ω is essential at first on-site diagnosis — the most common cause of intermittent communication errors when not installed.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- EEV Stuck — Reduced Cooling/Heating Capacity
- Indoor Unit Drain Pump Malfunction Causing Water Leak
- Indoor Unit Fan Abnormal Noise and Vibration
- Remote Control Reception Failure — Commands Not Transmitted
- Horizontal Indoor Unit Airflow Louver Malfunction
- Central Controller Indoor Unit Recognition Failure