Poor Temperature Recovery After Door Opening
Likely causes
Door gasket aged or damaged — cold air leakage
Check: A4 paper test: insert paper around entire door perimeter; sections with no resistance when pulling = leak point
What to do: Replace gasket (cut corners at 45°, use dedicated adhesive) → re-verify with A4 test → tighten hinge bolts to 15–20 N·m
PVC strip curtain damaged or not installed
Check: Check if strip curtain is installed and inspect for damage or hardening — verify 20cm width and 50% overlap standard
What to do: Replace with new PVC strip curtain (width 20cm, thickness 3mm, 50% overlap) → verify opening/closing resistance after installation
Reduced pull-down capacity — low refrigerant or compressor fault
Check: Measure pull-down time from +30°C to setpoint in empty cargo box — if 30% over design time, investigate
What to do: Check suction/discharge pressures → repair leak and recharge if low refrigerant → verify compressor current within ±10% of rated
Pre-cooling cargo before loading (2–3°C below setpoint) is the most effective way to maintain temperature during transit — the reefer unit is designed to maintain, not to chill, cargo.